TROUBLE SHOOTING OF TRANSFORMER
TROUBLE SHOOTING OF TRANSFORMER | |||
NO. | TROUBLES | CAUSE | ACTION |
1 | Stop of transformer (Except OLTC) | Internal fault of main tank | (1) Check on relay operation. (2) Electrical tests -1 Measurement of insulation resistance -2 Measurement of winding resistance -3 Measurement of voltage ratio. -4 Measurement of exciting current (3) Gas analysis of transformer |
1-1 | Operation of differntial relay and buchholz relay or pressure relief device operate simultaneously | (1) Internal fault | Action shall be same as internal fault procedures. |
1-2 | Operation of buchholz relay and pressure relief device | (2) Internal fault | Action shall be same as internal fault procedures. |
1-3 | simultaneously Operation of differential relay only | (1) Internal fault (2) Inrush current at time of energyization | (1) Action shall be same as internal fault procedures. (2)-1 Setting values of relays. (2)-2 Value of inrush current. |
1-4 | Operation of buchholz relay (trip) only | (1) Internal fault (2) Faulty operation | (1) Action shall be same as internal fault procedures. (2)-1 Check wiring. (2)-2 Check contacts. |
1-5 | Operation of pressure device Only | (1) Interal fault (2) Faulty Operation | (1) Action shall be same as internal fault procedures. (2)-1 Check wiring. (2)-2 Check contacts. |
1-6 | Winding temp. indicator or oil temp. indicator | (1) Internal fault (2) Faulty operation (3) Stop of cooling fan. | (1) Action shall be same as internal fault procedures. (2)-1 Check wiring (2)-2 Sudden variation of oil temperature. (3) Check cooling fan. |
2 | Operation of buchholz: relay (alarm) only | (1) Internal fault (2) Trapped air or evoluation of dissolved gases | (1) Action shall be same as internal fault procedures. (2) -1 Analysis of gas accumulated in Buchholz Relay. (2)-2 Sudden variation of oil temperature. |
3 | Operation of relays such as overcurrent relay, ground relay, arrestor etc. | (1) Internal fault (2) External faults such as short- circuit In the system | (1) Action shall be same as internal fault procedures. (2) -1 Check any sign of Heavy current circulation in the windings. (2) -2 Check any sign of on-load tap changer interrupting heavy short-circuit current. (2) -3 Short-circuit current value, its duration time. |
4 | Abnormality is found in recording devices | - ditto - | - ditto - |
High temperature rise | Period required to Reach the maximum temperature and ambient temperature, Load factor or type of load. Connection diagram of bank and internal connection tap voltage. | If the oil temperature is about 80`C over, the transformer must not be operated continuously. | |
Burned coil | Date and time of burning. Installation site. Perod of use(immediately after operation period). Cause of failure: Overload Lighting Short circuiting (internal or external) Others Existence or absense of copper powder. Operation of protective devices (primary and secondary) | ||
Local heating | Heated point. Load factor or type of load. Smoke. Discoloration. |
Insulation resistance failure | Insulation resistance: High voltage winding to low voltage winding and tank. Low voltage winding to high voltage winding and tank. High voltage winding to low voltage winding. Temperature and humidity at which mea surement is made. Installation site (indoors or outdoors). History of the transformer. Dielectric strangth of the insulation oil. | ||
Noise | Operating conditions (overload, normal) |
oZzy moved away ever before, I miss his cock, and
ReplyDeletei am always hungry for intercourse.
FUCK MY PUSSY!
My web site :: hcg injections
Also see my webpage > hcg injections
Mental
DeleteYou rеally make it sеem so еaѕу with yοur prеsentation but I find thіs matter to be гeally
ReplyDeletesomething that I thinκ I ωould neѵer undеrstand.
It ѕеems too сomplex anԁ еxtremеly broаd
for me. I am looking fогward foг yоur next post,
I will try to get the hang οf it!
My ωеb page ... ohm'S law
Hi boss
ReplyDeleteYou are mentioned Action shall be same as internal fault procedures what is that
Correct
ReplyDelete